info@opti-solar.com +886-2-2246-7272
Can I connect the diesel generator as the utility input source?
We could connect the diesel generator to our inverters as the condition below,
- Generator waveform THD: < 10%.
- Generator Vrms range: 180 ~ 270Vac
- Generator voltage crest factor(Vpeak/Vrms): < 1.6
- Generator peak voltage: <380V
- Frequency range: 45Hz ~ 63Hz
- Frequency slew rate: <0.3Hz/sec
Highly recommend the specification for the diesel generator.

For more information, please email service@opti-solar.com.